The Model 8220 is a single-phase AC + DC power meter with an electroluminescent backlit digital display. It is a measurement tool for electrical parameters and distribution network disturbances, enabling the user to obtain instant measurements of the main characteristics of a single-phase network (voltage, current, power, voltage and current harmonics, etc.) and to monitor machinery in operation (temperature, inrush current and duration of operation, distance of windings and rotational speed).
The Model 8220’s accuracy is better than 1% (excluding current sensors). It has a great flexibility due to AEMC’s range of current sensors, measuring from a few hundred milliamps to several thousand amps. Rated to 600V CAT III.
FEATURES
- Measures up to 660Vrms or Vdc
- Measures up to 6500Aac or 1400Adc(probe dependent)
- Displays Min, Max and Average Volts and Amps, Crest Factor, Peak Value and K-Factor
- Calculates and displays Watts, vars and VA, Power Factor and Displacement Power Factor for single-phase and balanced three-phase
- Measures and records power systems (kW, kVA, kvar)
- Energy metering (kAh, kvarh, kWh)
- Displays total harmonic distortion (THD-F and THD-R) for voltage and current
- Displays individual harmonic values and % for volts and amps through the 50thharmonic
- The Max and Min RMS measurements are calculated every half-period
- Captures and displays inrush current
- Calculates and displays phase rotation and RPM
- Displays temperature in both °F and °C
- Displays resistance up to 2000Ω
- Conducts continuity and diode tests
- Stores up to 99 complete sets of readings for all volt, amp, power and harmonic measurements
- Operates on batteries or optional power adapter
- Download stored data snapshots to DataView®software via optical USB cable (included)
- Includes FREE DataView® software for configuring data retrieval, real-time waveform display, analysis and report generation
SPECIFICATIONS
MODEL: 8220
Voltage (TRMS): Phase-to-Phase: 660V; Phase-to-Neutral: 600V
Current (TRMS): MN Clamp: 0.2 to 6A/120A or 2 to 240A MR Clamp: 10 to 1000Aac, 10 to 1400AdcSR Clamp: 3 to 1200A MiniFlex®: 10 to 1000AAmpFlex®: 10 to 6500A(1)
Frequency (Hz): 40 to 70Hz
Other Measurements: kW, kvar, PF, DPF, kVA, kWh, kvarh, VAh, Phase Rotation, Temperature, RPM, Resistance, Continuity, Diode Test
Harmonics: 1st to 50th
Sampling Frequency: 256 samples / cycle
Data Storage: Stores nine sets of readings totaling up to 99 snapshots for volts, amps, power and harmonics
Power Source: Six 1.5V AA Alkaline batteries (included)
Battery Life: ≥8 hrs with display on ≥40 hrs with display off (recording mode)
Communication Port: Optically isolated USB
Display: Three-line backlit color LCD digital display with custom icons and adjustable brightness & contrast
Dimensions: 8.3 x 4.3 x 2.4" (211 x 108 x 60mm)
Weight: 1.9lbs (0.88kg)
Safety Rating: EN 61010, 600V CAT III, IP54, Pollution Degree 2
(1)Crest factor at 6500 = 1
User Manual
Data Sheet
Brochure
Power Analyzers - Current Probe Specification Chart